DigiTMR S2

EHV Circuit Breaker Analyzer

The Vanguard DIGITMR S2 is an inexpensive, easy to use digital circuit breaker analyzer. The DIGITMR S2 can be operated stand-alone or can be computer-controlled. It can fully analyze a circuit-breaker’s performance by testing the contact time, stroke, velocity, over-travel, and contact wipe. Contact and motion analysis can be performed for all breaker contact operations (Open, Close, Open – Close, Close – Open, and Open – Close – Open). Timing results are recorded and displayed on the 240 x 128 pixels back-lit LCD screen and can also be printed on the built-in 4.5″ wide thermal printer.

  • Stand-alone, microcomputer-driven EHV Circuit Breaker Analyzer
  • Analyzes contact time, stroke, velocity, over-travel, and contact wipe
  • USB PC interface
  • USB Flash drive interface
  • Can store up to 200 test records and 100 test plans
  • Built-in thermal printer

 

TYPE portable digital circuit breaker analyzer
PHYSICAL SPECIFICATIONS18.5”W x 14”H x 7”D (47.0 cm x 35.7 cm x 17.6 cm); Weight: 20 lbs (9.1 kg)
INPUT POWER 3 Amps, 100 – 240 Vac, 50/60 Hz
DRY CONTACT OUTPUTS 3 dry-contact channels; each channel detects main contact and insertion resistor contact
TIMING WINDOWS1-second, 10-seconds, or 20-seconds
TIMING RESOLUTIONS±50 micro-seconds @ 1-second duration, ±500 micro-seconds @ 10-second duration, ±1.00 milli-second @ 20-second duration
TIMING ACCURACY0.05% of reading ±0.1 ms @ 1-second duration
CONTACT DETECTION RANGEClosed: less than 20 ohms; Open: greater than 5,000 ohm
RESISTOR DETECTION RANGE50 – 5,000 ohms
TRIGGER INPUT VOLTAGEOpen/Close: 30 – 300V, DC or peak AC
VOLTAGE SENSING INPUT RANGEV1: analog input; 0 – 255V, DC or peak AC; Sensitivity: ±1V V2: voltage presence/absence detector input; 30 – 300V, DC or peak AC
BREAKER OPERATIONSInitiate Open, Close, Open – Close, Close – Open, Open – Close – Open
BREAKER INITIATE CAPACITY30A, 250 Vac/dc max
INITIATE CURRENT READING RANGEOne, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5Khz
TRAVEL TRANSDUCER INPUT1 digital travel transducer channel; Linear range: 0.0 – 60.0 in (±0.005 in.); Rotary range: 0 – 360 degrees (±0.006 degrees)
CONTACT TRAVEL POINT DIFFERENCEMeasures “slow-close” contact-point distances; results can be printed
CT CURRENT SENSOROne, non-contact, 0 – 100A
DISPLAYBack-lit LCD screen (240 x 128 pixels); viewable in bright sunlight and low light levels
PRINTERBuilt-in 4.5-inch wide thermal printer can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGEStores up to 200 test records and 100 test plans
COMPUTER INTERFACESOne USB port, optional Bluetooth interface
PC SOFTWAREWindows®-based Vanguard Circuit Breaker Analysis (VCBA S2) software is included with purchase price. Software updates available at no additional charge.
SAFETYDesigned to meet UL/IEC 61010 and CAN/CSA C22.2 No. 1010.1-92 standards
ENVIRONMENTOperating: -10°C to 50° C (15°F to +122° F); Storage: -30° C to 70° C (-22°F to +158° F)
OPTIONSTransportation case (available for the DigiTMR S2 and the travel transducers)
WARRANTYOne year on parts and labor
DigiTMR S2 Datasheet (English)
Customer References
DigiTMR S2 User's Manual (English)
Bluetooth Connection Instructions
DigiTMR S2 Manual Del Usuario (Español)
VCBA S2 Software Manual (English)