CT-7000 S3

Digital Circuit Breaker Analyzer

The CT-7000 S3 is Vanguard’s fourth generation EHV circuit breaker analyzer. The CT-7000 S3 is available with 3 (part number 9021-UC) or 6 contact timing channels (part number 9100-UC). The CT-7000 S3 can fully analyze a circuit breaker’s performance by measuring the main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes. Both contact and motion analysis can be performed on all circuit breaker operations (OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN, and OPEN CLOSE-OPEN). The CT-7000 S3’s timing window is selectable between 1 second, 10 seconds, and 20 seconds.

  • Fully analyze circuit breaker’s performance by measuring main contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes
  • USB computer interface
  • USB Flash drive interface (Flash drive not included)
  • Store up to 200 test records and 100 test plans internally
  • Initiate Breaker Operation
  • Built-in 4.5″ wide Thermal Printer
  • Rugged “QWERTY” style membrane keypad
  • Optional “On-line” Timing Mode
  • Optional dual ground testing mode
  • Optional Bluetooth wireless computer interface

 

TYPE Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONSDimensions: 21.5”W x 8”H x 14” D (53 cm x 20 cm x 35 cm) Weight: 15 lbs (6.8 Kg)
INPUT POWER 100-240Vac, 3A, 50/60Hz
DRY CONTACT OUTPUTS 3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time.
TIMING WINDOWS 1 second, 10 seconds, or 20 seconds
TIMING RESOLUTIONS±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration
TIMING ACCURACY0.05% of reading ±0.05 ms @ 1 second duration
DRY-CONTACT CHANNEL PROTECTIONAll contact inputs are grounded until test. Input channels are also protected against static discharge.
DRY-CONTACT DETECTION RANGEClosed: Less than 20 Ohm. Opened: greater than 5000 ohm
INSERTION RESISTOR DETECTION RANGE50 – 5,000 ohms
TRIGGER INPUT VOLTAGEOpen/Close trigger voltage: 24 V – 300V DC or peak AC
VOLTAGE SENSING INPUT RANGEV1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC; record and print 3 timing events
BREAKER OPERATIONSInitiate Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY30A, 250 Vac/dc max
INITIATE CURRENT READING RANGEone, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
DIGITAL TRAVEL TRANSDUCER INPUTS3 channels, 200 ohm – 10K ohms
CONTACT TRAVEL POINT DIFFERENCEmeasures “slow-close” contact-point distances; results can be printed
DISPLAYback-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
PRINTERbuilt-in 4.5” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
INTERNAL TEST RECORD STORAGEStore up to 200 test records and 100 test plans
EXTERNAL TEST RECORD STORAGEUSB Flash drive interface for external storage of test records and test plans
COMPUTER INTERFACESOne USB port, optional Bluetooth wireless interface
PC SOFTWAREWindows® based Breaker Analysis software included with purchase price
CABLESfurnished with full set of test leads
OPTIONStransportation cases (available for the CT-7000 S3 and travel transducers), on-line timing mode, dual ground testing mode, bluetooth interface
SAFETYdesigned to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
ENVIRONMENTOperating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY90% RH @ 40°C (104°F) non-condensing
ALTITUDE2,000 m (6,562 ft) to full safety specifications
WARRANTYOne year on parts and labor
CT-7000 S3 Datasheet (English)
CT-7000 S3 User's Manual (English)
CT-7000 S3 Manual de Operacion (Español)
Safely Testing Circuit Breakers Using a Dual Ground Method
VCBA S2 Software Manual (English)
VCBA S2 Software Manual Del Usuario (Español)
Bluetooth Connection Instructions